Support Article

Intesis Panasonic PA-RC2-WMP comms problem in AUS/NZ

Issue of non-communication between Panansonic AC units and Intesis PA-RC2-WMP-1 when installed with a Panasonic keypad on the same bus.

Some Panasonic heatpumps in AU/NZ cannot support the power consumption of the Intesis gateway, it is not a problem of a particular unit, but appears to be intermittent.  

Issue solved by adding an Intesis power booster/ injector (external 15W 24V DC PSU also required)